4 hardware specifications – ProSoft Technology PS69-DPM User Manual

Page 107

Advertising
background image

PS69-DPM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 107 of 130

October 1, 2014

The maximum length of a bus segment depends on the baud rate used. Only PROFIBUS
certified cable, preferably the cable type A, should be used.

Baud rate in kBit/s

Max. Distance

9.6

1,200 m / 4000 ft

19.2

1,200 m / 4000 ft

93.75

1,200 m / 4000 ft

187.5

1,000 m / 3280 ft

500

400 m / 1300 ft

1,500

200 m / 650 ft

3,000

100 m / 325 ft

6,000

100 m / 325 ft

12,000

100 m / 325 ft

Parameter

Value

Impedance

135 to 65 Ohm

Capacity

< 30 pF/m

Loop resistance

110 Ohm/km

Wire gauge

0.64 mm

6.1.4 Hardware Specifications

Specification

Description

Processor

EC1-160P with integrated ASPC2

PROFIBUS Interface

RS-485, max. 12 MBaud, potential free, according EN
50170

Diagnostic Interface

RS232, PS/2 Mini DIN female connector, 9600 Baud, non
isolated

Power Supply

+5 V ±5 % / 260 mA

Max. Distance Rating

max. 6 modules to the power supply module

Dimensions

Standard 1769 Single-slot module

Burst

EN 61000-4-4, 2 kV, 5 kHz

Surge

EN 61000-4-5, 2 kV common mode, 1 kV differential
mode

ESD

EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect

Radiated/ Conducted
Immunity

EN 61000-4-3, 10 V/m, 30...1000 MHz, 80% AM, 1 kHz
sinewave
EN 61000-4-6, 10 V, 0,15...30 MHz

Radiated/ Conducted
Emission

EN 55011 Class A

Vibration/Shock

IEC 600068-2-6, 10-150 Hz, ± 0,75 mm, ± 1 g, 1
Octave/min
IEC 600068-2-27, 15 g, 11 ms

Operating Temp.

0 to 60°C (32 to 140°F)

Relative Humidity

5 to 95% (non-condensing)