ProSoft Technology PS69-DPM User Manual

Page 85

Advertising
background image

PS69-DPM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 85 of 130

October 1, 2014

CIP Message Parameters for MSAC1_Write

Parameter

Value

Remarks

Message Type

CIP Generic

Service Type

Custom

Service Code

64 hex

Service Code "Bridge Message"

Class

65 hex

CIP Object "CIP_MSG_BRIDGE""

Instance

1

Attribute

0

Source Element

WriteReq

Reference to a Tag of type MSAC1_WRITE_REQUEST

Destination

WriteCnf

Reference to a Tag of type
MSAC1_WRITE_CONFIRM

Source Length

16 + x
( x = 1 .. 240 )

16 = Constant part of the service MSAC1_WRITE_REQUEST
x = Number of data to be transferred

MSAL1M_Alarm_Res

The MSAL1M_Alarm_Res request is used by the master to send a DPV1 Alarm response to
a slave device. The message acknowledges the alarm when the appropriate indication
appears in theDPV1 Alarm Indication (page 67) area. The information mapped to this area
must be used in the DPV1 Alarm Response message in order to process the alarm properly.
The mapping of this information shall be as follows.

MSAL1M_ALARM_RES_REQUEST

Parameter

Data Type

Value

Description

Reserved1

INT

0

Reserved

Reserved2

INT

0

Reserved

Reserved3

INT

0

Reserved

Command

SINT

18

Command for Service MSAL1M_Alarm_Res

Reserved4

SINT

0

Reserved

DeviceAdr

SINT

0.. 125

Address of the PROFIBUS Slave from DPV1 Alarm Indication
Register.

SlotNum

SINT

0.. 254

Slot Number from DPV1 Alarm Indication Register.

SeqNum

SINT

0.. 31

Sequence Number from DPV1 Alarm Indication Register.

AlarmType

SINT

1 to 6,32 to
126

Alarm Type from DPV1 Alarm Indication Register.

AlarmSpec

SINT

0..7

Alarm Spec from DPV1 Alarm Indication Register.

Reserved5

SINT

0

Reserved