MSAC1_READ_CONFIRM

Name

Data Type

Value

Description

Reserved1

INT

0

Reserved

Reserved2

INT

0

Reserved

Answer

SINT

17

Answer MSAC1_Read

Failure

SINT

E

Error, status (see following Section)

Reserved3

INT

0

Reserved

DeciceAdr

SINT

0.. 125

Address of the Slave

DataArea

SINT

0

Reserved

DataAdr

INT

0.. 254

Slot Number

DataIdx

SINT

0.. 254

Index

DataCnt

SINT

X
= 1.. 240

Length of the received data block

DataType

SINT

0

Reserved

Function

SINT

1

MSAC1_Read

if ‚Failure' = CON_AD
Data[0]

SINT

Error_Code_1

Data[1]

SINT

Error_Code_2

if ‚Failure' = 0
Data[0..x-1]

SINT

Data to be received from the Slave

CIP Message Parameters for MSAC1_Read

Parameter

Value

Remarks

Message Type

CIP Generic

Service Type

Custom

Service Code

64 hex

Service Code "Bridge Message"

Class

65 hex

CIP Object "CIP_MSG_BRIDGE"

Instance

1

Attribute

0

Source Element

ReadReq

Reference to a Tag of type
MSAC1_READ_REQUEST

Destination

ReadCnf

Reference to a Tag of type
MSAC1_READ_CONFIRM

Source Length

16

Corresponds to the size of the MSAC1_READ_REQUEST structure