PS69-DPM ♦ CompactLogix or MicroLogix Platform

Contents

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 65 of 130

October 1, 2014

Code

Indication

Source

Corrective Action

56

Non Existing Slave Parameters

Configuration

Execute download of configuration
database again.

57

Faulty Parameter Value in a Slave
Parameters

Configuration

Check GSD file for possible incorrect slave
parameterization values.

58

Duplicate Slave Address

Configuration

Check configured slave addresses in

project.

59

Projected Send Process Data Offset
Address of a Slave is Outside the

Limits of 0 to 255

Configuration

Check slave configuration in active project.

60

Projected Receive Process Data
Offset Address of a Slave is Outside

the Limits of 0 to 255

Configuration

Check slave configuration in active project.

61

Data-Areas of Slaves are
Overlapping in the Send Process

Data

Configuration

Check slave configuration in active project.

62

Data-Areas of Slaves are
Overlapping in the Receive Process

Data

Configuration

Check slave configuration in active project.

63

Unknown Process Data Handshake Master

Problem with master’s startup parameters.

64

Free RAM Exceeded

Master

Master has a hardware issue.

65

Faulty Slave Parameter Dataset

Configuration

Check GSD file for possible incorrect slave
parameterization datasets.

202

No Memory Segment Available

Master

Master has a hardware issue.

212

Faulty Reading of a Database

Configuration

Execute download of configuration
database again.

213

Structure Used by the Operating
System is Faulty

Master

Master has a hardware issue.

220

Software Watchdog Error

Host

Firmware watchdog has an error.

221

No Data Acknowledge in Process
Data Handshake

Host

Firmware is having trouble with Host
acknowledgement.

222

Master in Auto_Clear

Slave Device

The auto_clear mode was activated,
because one slave is missing during
runtime.

225

No Further Segments

Master

Contact hotline

ERROR_EVENT Codes for an Err_Rem_ Adr of not equal to 255

Code

Indication

Source

Corrective Action

2

Slave Station Reports Data
Overflow

Master Telegram

Check length of configured slave parameter
or configuration data.

3

Request Function of Master is not

Supported in the Slave

Master Telegram

Check if slave is PROFIBUS-DP norm

compatible.

9

No Answer, Although the Slave
must Respond with Data

Slave

Check configuration data of the slave and
compare it with the physical I/O data

length.

17

No Response from the Slave

Slave

Check bus cable, and bus address of slave.