ProSoft Technology PS69-DPM User Manual

Page 56

Advertising
background image

Contents

PS69-DPM ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 56 of 130

ProSoft Technology, Inc.

October 1, 2014

On the left side of the dialog set the focus to the slot number where the module is installed.
Set the focus to "Other - Requires I/O Card Type ID" from the available module types and
then double click on it.

2.4.2 Expansion General Configuration

The communications parameters for the module should be set as shown in the dialog below.

Expansion General Configuration

Value

Vendor

283

Product Type

12

Product Code

3

Series/Major Rev/Minor Rev

A

Input Words

44 + X (X = 0 ... 204)

Output Words

8 + Y (Y = 0... 240)

Extra Data Length

0

X = Number of Words configured for the Master module (PROFIBUS input data); input size can be in the range between 44 and 248
words
Y = Number of Words configured for the Master module (PROFIBUS output data); output size can be in the range between 8 and 248

words

 Vendor ID / Product Type / Product Code for the PS69-DPM module are as shown

below:

o

Vendor ID: 283

o

Product Code: 12

o

Product Code: 3

 Input Words: The input size must be at least 88 Bytes (44 Words). It must be large

enough to accommodate the status information required by the module, which is 88
Bytes (44 Words) plus the number of PROFIBUS input data. You can increase the size
of this area using the size of each Input module connected. The Input image starts with
byte 88.