PS69-DPM ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 90 of 130

ProSoft Technology, Inc.

October 1, 2014

MSAL1M_Alarm_Res

Failure

Significance

Error source Help

86 hex = REJ_INT

The alarm handler is not
initialized

DEVICE

No DPV1 capable device configured within the
card

87 hex = REJ_SRT

The alarm handler is currently
stopped

DEVICE

No DPV1 capable slave device is in process
data exchange with the DEVICE. Check if

network is running

88 hex = REJ_ENA

The alarm that shall be
acknowledged is not enabled in

slave parameter data

HOST

Enable the corresponding alarm in slave

configuration data set

89 hex = REJ_NPD The alarm that shall be

acknowledge is not pending on

a MSAL1_Alarm_Res

HOST

Check the parameter Alarm_Type and
Seq_Nr. Both must be equal to the

MSAL1_Alarm_ind parameter

9a hex = REJ_COM Unknown msg.b command

HOST

Correct the requested msg.b parameter of
message