Hardware diagnostics (led) – ProSoft Technology PS69-DPM User Manual

Page 96

Advertising
background image

Contents

PS69-DPM ♦ CompactLogix or MicroLogix Platform

User Manual

PROFIBUS DPV1 Master

Page 96 of 130

ProSoft Technology, Inc.

October 1, 2014

5.2

Hardware Diagnostics (LED)

The following section contains a description of the LED and their meaning for both the CPU
module and the PS69-DPM module.

5.2.1 CompactLogix

The following table shows the possible LED indications of the CompactLogix CPU.

Indicator

Color/Status

Description

RUN

Off

No task(s) running; controller in Program mode

Green

One or more tasks are running; controller is in the Run mode

FORCE

Off

No forces enabled

Amber

Forces enabled

Amber Flashing

One or more input or output addresses have been forced to an On or Off state,

but the forces have not been enabled.

OK

Off

No power applied

Green

Controller OK

Red flashing

Recoverable controller fault

Red

Non-recoverable controller fault:
Cycle power. The OK LED should change to flashing red.
If LED remains solid red, replace the controller.

I/O

Off

No activity; no I/O or communications configured

Green

Communicating to all devices

Green flashing

One or more devices not responding

Red flashing

Not communicating to any devices
controller faulted

5.2.2 MicroLogix 1500

To identify problems via possible LED indications of a MicroLogix 1500 controller refer to the
MicroLogix 1500 User Manuals section "Troubleshooting Your System". Here you will find a
detailed description of fault indications and possible reasons.