10.4 Flow Rate High/Low, High-High/Low-Low Alarm Output

To use the flow rate high/low alarm or high-high/low-low alarm output, follow the procedure below.

High / Low alarm setting

Refer to 8.2.23, “Flow Rate High/Low Alarm and High-High/Low-Low
Alarm”
and set the high alarm and/or low alarm to ON and set the limit value for
high and/or low alarm.
For alarms not used, set its setting to OFF.

High-High / Low-Low alarm setting

Refer to 8.2.23, “Flow Rate High/Low and High-High/Low-Low Alarm” and
set the high-high alarm and/or low-low alarm to ON and set the limit value for
high-high alarm and/or low-low alarm.
For alarms not used, set its setting to OFF.

DO setting

Refer to 8.2.18 "Digital Output" to set the Digital Output 1 (DO1) and
Digital Output 2 functions (DO2) for high alarm output/low output alarm or
high-high alarm output/ low-low alarm output.

In addition, set the alarm active status, either Normally Open or Normally Closed.