Multiple range high/low limit alarm output


Note 1: Range changes to Small range when range select signal is H level, and to Large range in L

level.

Note 2: High-high/low-low limit alarm is activated when Small range is selected. High/low limit

alarm is not output to display.
High/low limit alarm is activated when Large range is selected. High-high/low-low
limit alarm is not output to display.

Note 3: Alarm output state is the same state to which digital output 1 or 2 is set. When converter

power is OFF, contact output is OPEN.

Note 4: Each alarm set value % is the percent set to the first range.
Note 5: Hysteresis of each alarm is 2.5 % for the first range.

Example

When Large range and Small range are set as below:

Large range (Range 1):

1000 m

3

/h

Small range (Range 2):

500 m

3

/h

And you want to set alarm values as below:

Large range alarm set values

High limit value:

800 m

3

/h

Low limit value:

600 m

3

/h

Small range alarm set values

High-high limit value: 400 m

3

/h

Low-low limit value: 300 m

3

/h

Set the alarm set values as below:

High limit value:

80 % (800 m

3

/h

÷1000 m

3

/h=0.8)

Low limit value:

60 % (600 m

3

/h

÷1000 m

3

/h=0.6)

High-high limit value: 40 % (400 m

3

/h

÷1000 m

3

/h=0.4) See Note4.

Low-low limit value: 30 % (300 m

3

/h

÷1000 m

3

/h=0.3) See Note4


Low-low limit

High-high limit

Low limit

Flow rate

High limit

Small range (Range 2)

Large range (Range 1)

Alarm output ON

Alarm output ON

Alarm output ON

Alarm output ON

Alarm output ON

DI range select signal

Multiple range

High limit alarm output

DO1

Multiple range
Low limit alarm output

DO2

Time