●Digital input control signal

You can select the detective level of the digital input, as shown below, to control the totalizer
and pulse output.
(Only when the digital input function is set for totalizer control input)

Selection items

Digital input function setting

Totalizer control signal

CNT ST/SP

Totalizer START/STOP

H signal

Totalizer STOP

L signal

Totalizer START

L LEVEL

CNT RS/ST

Totalizer RESET/START

H signal

Totalizer START

L signal

Totalizer RESET

CNT ST/SP

Totalizer START/STOP

H signal

Totalizer START

L signal

Totalizer STOP

H LEVEL

CNT RS/ST

Totalizer RESET/START

H signal

Totalizer RESET

L signal

Totalizer START

●Changing the digital input function

The following is an example to change the Digital Input (DI) function from No use (NO
USE

) to Totalizer Start / Stop (CNT ST/SP).

Switch operation

Display example

Description

Select "DI FUNC" from the setting item
selection menu.

The current setting (NO USE in this
example) appears.

Then push .

* Pushing returns you to the menu
screen.

The switches at the bottom change.
( are shown.)
At the same time, the cursor appears.
(The item indicated by the cursor is
highlighted.)

Then push .

You can continue to change the setting item.
Push to change the selection
items.

: Selected item is scrolled up.

: Selected item is scrolled down.

When the desired item is selected, push

to set the item temporarily.