6 F 8 A 0 9 3 4

LF546 Converter Specifications

Input

Input signal:

Flow rate proportional signal from the detector

Digital input signal

Signal type:

20 to 30Vdc voltage signal

Input resistance: About 2.7k

Number of input points:

1

Digital input function: Select either of the following.

Range switching input: Large/Small range switching of unidirectional double range,

forward/reverse direction double range

Counter control input: Internal totalization counter start/stop/reset control

Output hold input: The current output and pulse output are kept to their preset

values.

Zero adjustment input: Start still water zero adjustment.

Output

Current output:

4 to 20mAdc (load resistance 750 or less)

Digital output 1:

Output type:

Transistor open collector

Capacity:

30Vdc, Max 200mA

Number of output points:

1

Digital output 2:

Output type:

Semiconductor contact signal

output
(no polarity)

Capacity:

150Vdc, Max. 150mA

150Vac (peak value), Max.

100mA

Number of output points :

1