5 digital i/o connections – Toshiba LF516 User Manual

Page 33

Advertising
background image


32

6 F 8 A 0 9 3 4

5.5 Digital I/O Connections

Digital I/O terminals consist of contact output terminals (DO1 and DO2), voltage signal input
terminal (DI), and signal common terminal (COM). Each terminal (DO1, DO2 and DI) is isolated from
internal circuits. Terminal (COM) is the signal common for the other three terminals (DO1, DO2 and DI).

Functions can be assigned for each terminal with the LCD control keys. See Chapter 10, “Digital I/O
Functions.”

To connect an electromagnetic relay or counter to the contact output terminal (DO1 or DO2), put a
surge-absorbing diode into the input circuit of the relay or counter. See Figure 5.3 for an example of
electromagnetic counter connection.


























Figure 5.3 Electromagnetic Counter Connection Example

Note 1: Use a surge-absorbing diode of the rating: current rating 1A and voltage rating 200 V

minimum.

Note 2: When a power supply-built-in electronic counter is used, the serge-absorbing diode is not

required.

Note2
Solidstate relay

Transistor open collector

COM

DI

DO2

DO1


Resistor

Note2
Photo-coupler


Note1
Surge-absorbing diode

Power supply
24 V dc

Electromagnetic counter

Note2
(Power supply-built-in electronic counter)

Converter

Advertising