Mounting the end feed, Series dpb busway installation & operation manual, Figure 3a – GE Industrial Solutions GE Zenith Series DPB User Manual

Page 17: Figure 4a

Advertising
background image

9

Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

MOUNTING THE END FEED

VERTICAL END FEED SUPPORT
Series DPB End Feed enclosures can be mounted in a number of ways. The recommended method for mounting Series DPB
End Feed enclosures is as shown in Figure 3. Four 3/8" threaded rods (see Figure 3A) secure the enclosure to the ceiling or to
Unistrut

TM

, and a standard busway hanger supports the Splice Extension. These need to be aligned and leveled to each other

so that the End Feed is completely level after installation.

HORIZONTAL END FEED SUPPORT
Series DPB End Feed enclosures can be horizontally mounted. The recommended method is similar to the vertical mounting
method and is shown in Figure 4 below. The enclosure is supported by four 3/8" threaded rods (see Figure 4A) secure the
enclosure to the ceiling or to Unistrut

TM

, and a standard busway hanger supports the Splice Extension. These need to be

aligned and leveled to each other so that the End Feed is completely level after installation.

UNISTRUT

TM

UNISTRUT

TM

THREADED ROD

THREADED ROD

END FEED

END FEED

VERTICAL BUSRAIL HANGER

HORIZONTAL BUSRAIL HANGER

END FEED OR

CEILING / UNISTRUT

TM

END FEED OR

CEILING / UNISTRUT

TM

Figure 3A

Figure 3 - Vertical End Feed Support

Figure 4A

Figure 4 - Horizontal End Feed Support

OPTIONAL BCMS

MONITORING MODULE

OPTIONAL BCMS

MONITORING MODULE

ON BOTTOM OF END FEED