Series DPB Busway Installation & Operation Manual

POWER CONNECTIONS

See Figure 52 - IX Display Interface Board for connection points.

120Vac

1.) Phase Voltage connects to TB1 pin 3
2.) Neutral Voltage connects to TB1 pin 1
3.) Ground connects to TB2 pin 3

24Vdc

1.) +24V connects to TB2 pin 1
2.) 24V return connects to TB2 Pin 2
3.) Ground connects to TB2 pin 3

Figure 52 - IX Display Interface Board

TB1

TB2

1 2 3

1 2 3