GE Industrial Solutions GE Zenith Series DPB User Manual
Page 69
61
Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
Series DPB Busway Installation & Operation Manual
M
odbus
M
ode
V
ia
Rs422
V
ia
e
theRnet
Routing
- Communication
Serial
TCP
- Mode
Transparent
Transparent
- Timeout
5s
5s
- Serial Port
Com4
Com4
- Baud
9600
9600
- Parity
Even
Even
- Data bits
8
8
- Stop bits
1
1
- Ethernet Port
502
502
5.) To change from RS422 to Ethernet, change the “Communication” box under Routing
from “Serial” to “TCP” or vice versa.
6.) Press “OK” on the PROPERTIES box. You may need to drag the box up to see the “OK” button.
7.) Press “OK” on the CHANGE ACTIVE CONTROLLER box.
8.) Press “OK” on the PROJECT MUST RESTART box.
9.) Press the “Reset” button. The reset button is recessed in a small hold on the left side
of the bottom of the enclosure
10.) Wait for the unit to reboot.