Series DPB Busway Installation & Operation Manual

MODBUS CONNECTIONS ON IX DISPLAY INTERFACE BOARD

See Figure 54 for MODBUS Connections on IX Display Interface Board

Downstream Connection utilize Connector TB3 - Connects to End Feed Daisy Chain

1.) Transmit + is TB3 pin 1
2.) Transmit - is TB3 pin 2
3.) Receive + is TB3 pin 3
4.) Receive - is TB3 pin 4
5.) Ground is TB3 pin 5

Upstream Connections utilize Connector TB4 - Connects to customer's building management system.

1.) Transmit + is TB4 pin 1
2.) Transmit - is TB4 pin 2
3.) Receive + is TB4 pin 3
4.) Receive - is TB4 pin 4
5.) Ground is TB4 pin 5

TB3

TB4

1 2 3 4 5

1 2 3 4 5

Figure 54 - Connections on IX Display Interface Board