Series dpb busway installation & operation manual – GE Industrial Solutions GE Zenith Series DPB User Manual

Page 72

Advertising
background image

64

Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

BCMS Basic = Current Only
BCMS Plus = Current + Voltage

PERSONALIZATION

PARAMETER

DESCRIPTION

RESOLUTION

NOTES

BCMS

BASIC

BCMS

PLUS

Circuit Breaker Size:

Output circuit breaker rating

1 A.

Defines output circuit breaker ratings;
default is 20 A ; (20-100 A range)

a

a

Warning Time Delay:

Time (seconds) before warn-
ing alarm activates

0-60 seconds

Defines duration current must
exceed threshold before activating
a current warning alarm; default is 0
seconds

a

a

Alarm Time Delay:

Time (seconds) before alarm
activates

0-60 seconds

Defines duration current must
exceed threshold before activating
a high current alarm; default is 10
seconds

a

a

Demand Average Time:

Time (seconds) to

determine average current

1 second

Defines time by which average
current is determined; default is 15
seconds. Range is 15 - 60 seconds

a

a

Current Warning Alarm:

Circuit breaker current first
level alarm

40-100%

Defines threshold based on a
percentage of circuit breaker rating
(default is 70%) to activate current
warning alarm after a time delay
(default is zero seconds)

a

a

Current High Alarm:

Circuit breaker current
second level alarm

50-100%

Defines threshold based on a
percentage of circuit breaker rating
(default is 85%) to activate high cur-
rent alarm after a time delay (default
is 10 seconds)

a

a

Voltage Range:

Source voltage

0.1 V

Defines monitored voltage (208, 480,
600 VAC)

a

Frequency:

Source frequency

0.1 Hz

Defines frequency (60 Hz or 50 Hz)

a

Board Name Personal-
ization:

User defined device name

Alphanumeric

Device name; 16 Character maxi-
mum

a

Overvoltage Alarm:

High voltage detected on
source

0.1V

Defines voltage to activate over volt-
age alarm .(default is 200 VAC)

a

Undervoltage Alarm:

Low voltage detected on
source

0.1V

Defines voltage to activate under
voltage alarm (default is 60 VAC)

a

Advertising