Series dpb busway installation & operation manual – GE Industrial Solutions GE Zenith Series DPB User Manual

Page 73

Advertising
background image

65

Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

APPENDIX B: END FEED (INPUT PM PCB) MONITORING

SPECIFICATIONS

BCMS Basic = Current Only
BCMS Plus = Current + Voltage

MONITORED PARAMETERS

PARAMETER

DESCRIPTION

RESO-

LUTION

NOTES

BCMS

BASIC

BCMS

PLUS

Current (A):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

1

0.1 A

Input source current(s); neutral and ground
current optional

a

a

Maximum Current (A):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

1

0.1 A

Maximum input current detected per phase

a

a

Minimum Current (A):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

1

0.1 A

Minimum input current detected per phase

a

a

Current (A):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

1

0.1 A

Average input current monitored over 15-60
minutes rolling average (user defined)

a

a

Percent Load Utiliza-
tion (%):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

0.1%

Percentage of maximum circuit breaker
current utilization. Requires personalization
of circuit breaker current rating

a

a

Voltage Source 1 and
2 (VAC):

A, B, C Phase (L-L, L-N) –
source 1;
A, B, C Phase (L-L, L-N) –
source 2

0.1 VAC

Input source voltage(s)

a

Crest Factor
(Peak A RMS):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

0.001 A

Peak waveform current divided by average
RMS current of the waveform; per phase

a

Real Power (kW):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

0.01 kW

kW (real power) per phase

a

Apparent Power (kVA):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

0.01 kVA kVA (apparent power) per phase

a

Reactive Power (kVAR):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

0.01
kVAR

kVAR (reactive power) per phase

a

Power Factor (PF):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

0.01 PF

Load Power Factor per phase

a

Energy Usage (kWh):

A, B, C (circuit breaker 1);
A, B, C (circuit breaker 2)

0.01 kW

Energy consumption per phase

a

Total Harmonic
Distortion (%THD):

A, B, C Phase (source1);
A, B, C Phase (source2);

0.1%

Total Harmonic Distortion (load) per phase
measured to 3

rd

, 5

th

, 7

th

, 9

th

, 11

th

, 13

th

harmonics

a

Frequency (Hz):

A phase (40 – 70 Hz)

0.1 Hz

Source frequency as measured from phase
A

a

1

Neutral and Ground currents may be monitored in addition to phase currents; see note on neutral and ground current monitoring.