Series DPB Busway Installation & Operation Manual

113�

R

Power Factor, Breaker 1B & 2B

114�

R

Power Factor, Breaker 1C & 2C

These registers are circuit Phase Kilowatt Hours per phase� Values are in kilowatts hours (90 = 90kwh) For
KWH 32-bit value multiply High-word integer by 2^16 (65536) and add Low-word integer�
115�

R

NV

KWH High-word integer, Breaker 1A

116�

R

NV

KWH Low-word integer, Breaker 1A

117�

R

NV

KWH High-word integer, Breaker 1B

118�

R

NV

KWH Low-word integer, Breaker 1B

119�

R

NV

KWH High-word integer, Breaker 1C

120�

R

NV

KWH Low-word integer, Breaker 1C

121�

R

NV

KWH High-word integer, Breaker 2A

122�

R

NV

KWH Low-word integer, Breaker 2A

123�

R

NV

KWH High-word integer, Breaker 2B

124�

R

NV

KWH Low-word integer, Breaker 2B

125�

R

NV

KWH High-word integer, Breaker 2C

126�

R

NV

KWH Low-word integer, Breaker 2C

127�

R

NV

KWH High-word integer, Breaker 1A & 2A

128�

R

NV

KWH Low-word integer, Breaker 1A & 2A

129�

R

NV

KWH High-word integer, Breaker 1B & 2B

130�

R

NV

KWH Low-word integer, Breaker 1B & 2B

131�

R

NV

KWH High-word integer, Breaker 1C & 2C

132.

R

NV

KWH Low-word integer, Breaker 1C & 2C

Writing this register will reset all KWH registers to zero�
133�

W

KWH

Reset

Bus connection temperature given in degrees Celsius (24 = 24 ºC) or Fahrenheit (75 = 75 ºF)�
134�

R Temperature

Board

135�

R Temperature

1

136�

R Temperature

2

137�

R Temperature

3

138�

R Temperature

4

139�

R Max

Temperature

Board

140�

R Max

Temperature

1

141�

R Max

Temperature

2

142�

R Max

Temperature

3

143.

R Max

Temperature

4

144.

R Min

Temperature

Board

145.

R Min

Temperature

1

146.

R Min

Temperature

2

147.

R Min

Temperature

3

148.

R Min

Temperature

4

This register gives the over temperature threshold for the board given in degrees Celsius (24 = 24 ºC) or
Fahrenheit (75 = 75 ºF)� Default for Temperature threshold for board is 80 ºC and for the Bus Temperature
thresholds is 120 ºC�

149�

R/W

Over

Temperature

threshold

150�

R/W

Under

Temperature

threshold