Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

78�

R

Percent load phase 2C

These registers show crest factor per phase� Values are peak current/rms current with three decimal places
(1412 = 1�412)�
79�

R

Crest Factor phase 1A

80�

R

Crest Factor phase 1B

81�

R

Crest Factor phase 1C

82�

R

Crest Factor phase 2A

83�

R

Crest Factor phase 2B

84�

R

Crest Factor phase 2C

The following Warning Register sets a bit for every channel, which reads a current above the Warning
Threshold for at least the Warning Time-Delay� All warnings are latching and must be reset by the controller�
To reset any alarm, read the register and the write the register with the desired alarm bit cleared�
85�

R/W

NV

Warning Register (Latching)

bit

0:

Phase

1A

bit

1:

Phase

1B

bit

2:

Phase

1C

bit

3:

Phase

2A

bit

4:

Phase

2B

bit

5:

Phase

2C

bits 6 – 15: Not Used Always read as 0

The following Alarm Register sets a bit for every channel, which reads a current above the Alarm Threshold for
at least the Alarm Time-Delay� All alarms are latching and must be reset by the controller� To reset any alarm,
read the register and then write the register with the desired alarm bit cleared�
86�

R/W

NV

Alarm Register (Latching)

bit

0:

Phase

1A

bit

1:

Phase

1B

bit

2:

Phase

1C

bit

3:

Phase

2A

bit

4:

Phase

2B

bit

5:

Phase

2C

bits 6 – 15: Not Used Always read as 0

The following Warning Threshold register sets the thresholds for the Warning alarms� A Warning alarm is
given in percent of the Full load registers (75 = 75%)� A Warning alarm will occur if the measured current is
above the Warning Threshold for at least the Warning Time Delay� Default for the Warning thresholds is 70%�
The Values that are written to the Warning Threshold must be between 40 and 100 and always below the
corresponding Alarm Threshold�

87�

R/W

NV

Warning Threshold

The following Alarm Threshold registers set the thresholds for the Alarms� A Alarm Threshold register is given
in percent of the Full Load registers (85 = 85%)� An Alarm will occur if the measured current is above the Alarm
Threshold for at least the Alarm Time Delay� Default for the Alarm thresholds is 80%� The Values that are
written to the Alarm Threshold must be between 50 and 100 and always above the corresponding Warning
Threshold�

88�

R/W

NV

Alarm Threshold