GE Industrial Solutions GE Zenith Series DPB User Manual

Page 88

Advertising
background image

80

Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

42�

W

Min/Max

Reset

The following Breaker Size Registers set the capacity of each breaker for the alarms� Units are in Amps (20
= 20 Amps)� The values that can be written are between 15 and 100� The Default value is -1 (65535)� If the
breaker is -1 (65535) then no alarm for this breaker will be given� This can be done by giving the breaker a size
0� For three two phase breakers, see Note on the Current Points above�
43�

R/W

NV

Breaker

Size

1A

44�

R/W

NV

Breaker

Size

1B

45�

R/W

NV

Breaker

Size

1C

46�

R/W

NV

Breaker

Size

2A

47�

R/W

NV

Breaker

Size

2B

48�

R/W

NV

Breaker

Size

2C

Writing to this register will set all the Breakers size registers to the value written� The Values that are written
to the Breaker sizes must be either zero or between 15 and 100� To remove all breakers, give a value of 0� This
register should always read 0�
49�

W

Global

Breaker

Size

These registers show current demand per phase and are in tenth of amps (260 = 26�0 Amps)� Values are the
average current over the time given in the Demand Register�
50�

R Demand

phase

1A

51�

R Demand

phase

1B

52�

R Demand

phase

1C

53�

R Demand

phase

2A

54�

R Demand

phase

2B

55�

R Demand

phase

2C

The Demand Register is time that the demand is averaged over in minutes� It must be between 15 to 60
minutes� The Default is 15 minutes�
56�

R/W

NV

Demand

time

These registers show Percent load and is given in tenth of a percent (753 = 75�3%)� These percents are the
Amps per phase divided by the breaker size of the same phase�
57�

R Percent

load

Breaker

1A

58�

R Percent

load

Breaker

1B

59�

R Percent

load

Breaker

1C

60�

R Percent

load

Breaker

2A

61�

R Percent

load

Breaker

2B

62�

R Percent

load

Breaker

2C

These registers show crest factor per phase� Values are peak current/rms current with three decimal places
(1412 = 1�412)�
63�

R Crest

Factor

Breaker

1A

64�

R Crest

Factor

Breaker

1B

65�

R Crest

Factor

Breaker

1C

66�

R Crest

Factor

Breaker

2A

67�

R Crest

Factor

Breaker

2B

68�

R Crest

Factor

Breaker

2C