Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0
GE Confidential
Series DPB Busway Installation & Operation Manual
CHANGE MODBUS RTU FROM RS422 TO VIA ETHERNET
1.) On the SETUP screen press the “Modbus Setup” button.
2.) Enter User ID and Password, and press the “Modbus Setup” button again.
3.) From the CHANGE ACTIVE CONTROLLER screen, Select “ModbusMaster”
so it is highlighted, and press “Settings” buton.
4.) The settings should look like the following:
M
odbus
M
ode
V
ia
Rs422
V
ia
e
theRnet
Settings
- Communication Mode
Serial
Serial
- Default Station
1
1
- Modbus Protocol
RTU
RTU
- 32bit Work Mapping
Motorola
Motorola
- Addressing
Decimal
Decimal
- Start Address
1-based
1-based
- Max Block Size (words)
16
16
- Force Function Code 0x10
Disabled
Disabled
- String Swap
Disabled
Disabled
- Silent Time (ms)
1
1
- Clock Register
0
0
- Serial
- Port
Com2
Com2
- Baud
9600
9600
- Parity
Even
Even
- Data bits
8
8
- Stop bits
1
1
Advanced
- Enable Unicode
False
False
- Byte Order
Intel
Intel
- Timeout
400
400
- Retries
3
3
- Offline station retry time
10
10
- Hide Comm. Error
False
False
- Command Line Option