63

Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

BCMS Basic = Current Only
BCMS Plus = Current + Voltage

ALARM PARAMETERS

ALARM

DESCRIPTION

NOTES

BCMS

BASIC

BCMS

PLUS

Current Loss /
Zero Current:

A,B,C (circuit breaker 1),
A,B,C (circuit breaker 2)

Activated when current goes above 1.5 A then to zero
Amps; can signify tripped or open circuit breaker or loss of
input current

a

a

Current Warning Alarm:

A,B,C (circuit breaker 1),
A,B,C (circuit breaker 2)

User defined based on a percentage of circuit breaker
rating; default is 70%

Alarms when current exceeds threshold after time delay
(default is zero seconds )

a

a

Current High Alarm:

A,B,C (circuit breaker 1),
A,B,C (circuit breaker 2)

User defined based on a percentage of circuit breaker
rating(default is 85%); alarms when current exceeds
threshold after time delay; default is 10 seconds

Typically used to indicate when circuit approached trip
threshold

a

a

Global Alarms:

Current Warning Alarm

Indicates if any current warning alarm is active

a

a

High Current Alarm

Indicates if any high current alarm is active

a

a

Zero Current Alarm

Indicates if any zero current alarm is active (indicates
breaker trip or breaker open or loss of source)

a

a

Overvoltage Alarm

Indicates if any over voltage alarm is active

a

Undervoltage Alarm

Indicates if any under voltage alarm is active

a

Over Temperature Alarm

Indicates if any over temperature alarm is active

a

Under Temperature Alarm

Indicates if any under temperature alarm is active

a

Overvoltage Alarm:

(L-N Voltage)

User defined; default is 200 VAC; no time delay

a

Undervoltage Alarm:

(L-N Voltage)

User defined; default is 120 VAC

a