Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

APPENDIX D: POINTS LIST FOR THE END FEED INPUT PM PCB

All Modbus variables are stored in 16-bit integer format.

#

R/W

NV

Description

These registers show the Main voltages and are in tents of a volt (1215 = 121.5 Amps)
1.

R/W

Main

Voltage1, phase AB

2.

R/W

Main

Voltage1, phase BC

3.

R/W

Main

Voltage1, phase CA

4.

R/W

Main

Voltage1, phase AN

5.

R/W

Main

Voltage1, phase BN

6.

R/W

Main

Voltage1, phase CN

7.

R/W

Main

Voltage2, phase AB

8.

R/W

Main

Voltage2, phase BC

9.

R/W

Main

Voltage2, phase CA

10.

R/W

Main

Voltage2, phase AN

11.

R/W

Main

Voltage2, phase BN

12.

R/W

Main

Voltage2, phase CN

An Over Voltage Alarm occurs if the Any L-N voltage is greater than this threshold register at any time and is
given in tenths of a volt (1200 = 120.0 Volts). For Defaults see the Voltage Type register.

13.

R/W

NV

Over Voltage Alarm Threshold Main

An Under Voltage Alarm occurs if the Any L-N voltage is less than this threshold register at any time and is given
in tenths of a volt (1200 = 120.0 Volts) For Defaults see the Voltage Type register.

14.

R/W

NV

Under Voltage Alarm Threshold Main

Frequency is measured from the phase A voltage input. Range is 40.0-70.0Hz: This register will read as 0xFFFF if
frequencies outside of this range or if sufficient voltage is not present on phase A for an accurate determination.

15.

R

Frequency

These registers show Total Harmonic Distortion (THD) calculations and are given in tenth of a percent (01 = 0.1%).

16.

R

Main

Voltage1, phase A THD

17.

R

Main

Voltage1, phase B THD

18.

R

Main

Voltage1, phase C THD

19.

R

Main

Voltage2, phase A THD

20.

R

Main

Voltage2, phase B THD

21.

R

Main

Voltage2, phase C THD