Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

If your voltage is between the limits, pick the Higher Limit�

13�

R/W

NV

Voltage Type (208, 380, 400, 415, 480, 600)

This register shows the setting for the Voltage monitoring setup� A set bit indicated active value�
14�

R/W

NV

Voltage

Option

Setting

bit

0:

Voltage

option

set

bit

1:

Set

for

50

Hz

bit

2:

External

LED

blink

bit

3:

Auto

Adjust

Gain�

bits 4 – 15: Not Used Always read as 0

These registers show the phase currents and are given in tenth of amps (100 = 10�0 Amps)

NOTE: If there are three two phase breakers, the center breaker’s current will be showed as Current, Breaker

1C & 2A.
15�

R/W

Current,

Breaker

1A

16�

R/W

Current,

Breaker

1B

17�

R/W

Current,

Breaker

1C

18�

R/W

Current,

Breaker

2A

19�

R/W

Current,

Breaker

2B

20�

R/W

Current,

Breaker

2C

21�

R

Current, Breakers 1A & 2A

22�

R

Current, Breakers 1B & 2B

23�

R

Current, Breakers 1C & 2C

These registers show the minimum phase currents and are in tenth of amps (100 = 10�0 Amps)� For three two
phase breakers, see Note on the Current Points above�
24�

R Minimum

Current,

Breaker

1A

25�

R Minimum

Current,

Breaker

1B

26�

R Minimum

Current,

Breaker

1C

27�

R Minimum

Current,

Breaker

2A

28�

R Minimum

Current,

Breaker

2B

29�

R Minimum

Current,

Breaker

2C

30�

R

Minimum Current, Breakers 1A & 2A

31�

R

Minimum Current, Breakers 1B & 2B

32�

R

Minimum Current, Breakers 1C & 2C

These registers show the maximum phase currents and are in tenth of amps (100 = 10�0 Amps)� For three
two phase breakers, see Note on the Current Points above�
33�

R Maximum

Current,

Breaker

1A

34�

R Maximum

Current,

Breaker

1B

35�

R Maximum

Current,

Breaker

1C

36�

R Maximum

Current,

Breaker

2A

37�

R Maximum

Current,

Breaker

2B

38�

R Maximum

Current,

Breaker

2C

39�

R

Maximum Current, Breakers 1A & 2A

40�

R

Maximum Current, Breakers 1B & 2B

41�

R

Maximum Current, Breakers 1C & 2C

Writing to this register will reset all Min and Max registers to currents present value�