Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

The Warning Time Delay register set the minimum time required for the current to exist above the Warning
Threshold before the Warning alarm in set� Units are in seconds� The Values that are written to the Warning
Time Delays must be between 0-60� The Default is 0 (zero) which means that there is no delay for the Warning
alarm�
89�

R/W

NV

Warning Time Delay

The Alarm Time Delay register set the minimum time required for the current to exist above the alarm
Threshold before the Alarm is set� Units are in seconds� The Values that are written to the Alarm Time Delays
must be between 0-60� The Default is 10 which means that there is ten seconds before an Alarm is given�
90�

R/W

NV

Alarm Time Delay

This register provides a quick status of alarms for the unit� A bit in this register is set if any bit in the indicated
register is set�
91�

R

NV

Global Warning/Alarm Register

bit

0:

Warning

Register

bit

1:

Alarm

Register

bit

2:

Over

Voltage

Side

1

bit

3:

Under

Voltage

Side

1

bit

4:

Over

Voltage

Side

2

bit

5:

Under

Voltage

Side

2

bits 4 – 15: Not Used Always read as 0

These alarms are latching and must be cleared by the user� To reset any alarm, read the register and then
write the register with the desired alarm bit cleared� Writing a 1 to any bit has no effect�
92�

R/W

NV

Meter Alarm Status (Latching)

bit 0: Over Voltage Phase A Side 1

bit 1: Over Voltage Phase B Side 1

bit 2: Over Voltage Phase C Side 1

bit 3: Under Voltage Phase A Side 1

bit 4: Under Voltage Phase B Side 1

bit 5: Under Voltage Phase C Side 1

bit 6: Over Voltage Phase A Side 2

bit 7: Over Voltage Phase B Side 2

bit 8: Over Voltage Phase C Side 2

bit 9: Under Voltage Phase A Side 2

bit 10: Under Voltage Phase B Side 2

bit 11: Under Voltage Phase C Side 2

bits 10 – 15: Not Used Always read as 0

This register is the four Digital alarm that can be used by the customer�
93�

R

Digital alarm status

bit

0:

Digital

alarm

1

bit

1:

Digital

alarm

2

bit

2:

Digital

alarm

3

bit

3:

Digital

alarm

4

bits 4 – 15: Not Used Always read as 0