Series DPB Busway Installation & Operation Manual

This register shows what Voltage values that are being read by this board�

Note Maximum Minimum Default Limits for each Voltage Type are:

208

Phase to Phase

High 239

Low 177

Neutral

High 138

Low 102

380

Phase to Phase

High 437

Low 323

Phase to Neutral

High 252

Low 186

400

Phase to Phase

High 460

Low 340

Phase to Neutral

High 265

Low 196

415

Phase to Phase

High 518

Low 383

Neutral

High 299

Low 221

480

Phase to Phase

High 552

Low 408

Phase to Neutral

High 319

Low 236

600

Phase to Phase

High 690

Low 510

Phase to Neutral

High 398

Low 295

If your voltage is between the limits, pick the Higher Limit�

22�

R/W

NV

Voltage Type (208, 380, 400, 415, 480, 600)

This register shows the setting for the Voltage monitoring setup� A set bit indicated active value�
23�

R/W

NV

Voltage Option Setting

bit 0: Voltage option side 1 set

bit 1: Voltage option side 2 set

bit

2:

Set

for

50

Hz

bit

3:

Auto

Adjust

Gain�

bits 4 – 15: Not Used Always read as 0

These registers show the phase currents and are given in tenth of amps (100 = 10�0 Amps)
Note: For Neutral and Ground options see Current Options and read the note with these options�
24�

R/W

Current,

Phase

1A

25�

R/W

Current, Phase 1B

26�

R/W

Current, Phase 1C

27�

R/W

Current, Side 1 Neutral (option)

28�

R/W

Current, Side 1 Ground (option)

29�

R/W

Current, Phase 2A

30�

R/W

Current, Phase 2B

31�

R/W

Current, Phase 2C

32�

R/W

Current, Side 2 Neutral (option)

33�

R/W

Current, Side 2 Ground (option)

34�

R

Current, Phases 1A & 2A

35�

R

Current, Phases 1B & 2B

36�

R

Current, Phases 1C & 2C


These registers show the minimum phase currents and are in tenth of amps (100 = 10�0 Amps)
37�

R

Minimum Current, Phase 1A

38�

R

Minimum Current, Phase 1B

39�

R

Minimum Current, Phase 1C

40�

R

Minimum Current, Phase 1N

41�

R

Minimum Current, Phase 1G

42�

R

Minimum Current, Phase 2A

43�

R

Minimum Current, Phase 2B

Advertising