measured current is above the Alarm Threshold for at least the Alarm Time Delay� Default for the Alarm
thresholds is 80%� The Values that are written to the Alarm Threshold must be between 50 and 100 and
always above the corresponding Warning Threshold�

73�

R/W

NV

Alarm

Threshold

The Warning Time Delay register set the minimum time required for the current to exist above the Warning
Threshold before the Warning alarm in set� Units are in seconds� The Values that are written to the Warning
Time Delays must be between 0-60� The Default is 0 (zero) which means that there is no delay for the Warning
alarm�

74�

R/W

NV

Warning

Time

Delay

The Alarm Time Delay register set the minimum time required for the current to exist above the alarm
Threshold before the Alarm is set� Units are in seconds� The Values that are written to the Alarm Time Delays
must be between 0-60� The Default is 10 which means that there is ten seconds before an Alarm is given�

75�

R/W

NV

Alarm

Time

Delay

This register provides a quick status of alarms for the unit� A bit in this register is set if any bit in the indicated
register is set�

76�

R NV

Global

Alarm

Register

bit

0:

Warning

Register

bit

1:

Alarm

Register

bit

2:

Zero

Current

Register

bit

3:

Over

Voltage

bit

4:

Under

Voltage

bit

5:

Over

Temperature

bit

6:

Under

Temperature

bits 7 – 15: Not Used Always read as 0

These alarms are latching and must be cleared by the user� To reset any alarm, read the register and then
write the register with the desired alarm bit cleared� Writing a 1 to any bit has no effect�

77�

R/W

NV

Meter Alarm Status (Latching)

bit

0:

Over

Voltage

Phase

A

bit

1:

Over

Voltage

Phase

B

it

2:

Over

Voltage

Phase

C

bit

3:

Under

Voltage

Phase

A

bit

4:

Under

Voltage

Phase

B

bit

5:

Under

Voltage

Phase

C

bit

6:

Over

Temperature

Board

bit

7:

Over

Temperature

1

bit

8:

Over

Temperature

2

bit

9:

Over

Temperature

3

bit

10:

Over

Temperature

4

bit

11:

Under

Temperature

Board

bit

12:

Under

Temperature

1

bit

13:

Under

Temperature

2

bit

14:

Under

Temperature

3