Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

bit

15:

Under

Temperature

4

This register shows the setting for the Temperature and Current monitoring setup� A set bit indicated active value�
78�

R/W

NV

Current

Option

Setting

bit

0:

Flip

Current

for

Strip

1

bit

1:

Flip

Current

for

Strip

2

bit

2:

Temperature

in

Fahrenheit

bits 3 – 14: Not Used Always read as 0

bit

15

Current

Loss

These registers show the KW and are in hundredth of KW (500 = 5�00 KW)
79�

R KW,

Breaker

1A

80�

R KW,

Breaker

1B

81�

R KW,

Breaker

1C

82�

R KW,

Breaker

2A

83�

R KW,

Breaker

2B

84�

R

KW,

Breaker

2C

85�

R

KW, Breakers 1A & 2A

86�

R

KW, Breakers 1B & 2B

87�

R

KW, Breakers 1C & 2C

KVA Registers 88-96 are in hundredth of KVA (500 = 5�00 KVA)
88�

R KVA,

Breaker

1A

89�

R KVA,

Breaker

1B

90�

R KVA,

Breaker

1C

91�

R KVA,

Breaker

2A

92�

R KVA,

Breaker

2B

93�

R KVA,

Breaker

2C

94�

R

KVA, Breakers 1A & 2A

95�

R

KVA, Breakers 1B & 2B

96�

R

KVA, Breakers 1C & 2C

KVAR Registers 97-105 are in hundredth of KVAR (500 = 5�00 KVAR)
97�

R KVAR,

Breaker

1A

98�

R KVAR,

Breaker

1B

99�

R KVAR,

Breaker

1C

100�

R KVAR,

Breaker

2A

101�

R KVAR,

Breaker

2B

102�

R KVAR,

Breaker

2C

103�

R

KVAR, Breakers 1A & 2A

104�

R

KVAR, Breakers 1B & 2B

105�

R

KVAR, Breakers 1C & 2C

Power Factor Registers 106-114 are in hundredth of PF (98 = 0�98 PF)
106�

R Power

Factor,

Breaker

1A

107�

R Power

Factor,

Breaker

1B

108�

R Power

Factor,

Breaker

1C

109�

R Power

Factor,

Breaker

2A

110�

R Power

Factor,

Breaker

2B

111�

R Power

Factor,

Breaker

2C

112�

R

Power Factor, Breaker 1A & 2A