Series DPB Busway Installation & Operation Manual

BCMS Basic = Current Only
BCMS Plus = Current + Voltage

ALARM PARAMETERS

PARAMETER

DESCRIPTION

NOTES

BCMS

BASIC

BCMS

PLUS

Current Warning Alarm:



A, B, C (circuit breaker 1),
A, B, C (circuit breaker 2)

Indicates current exceeds user defined threshold (ex-
pressed as a percentage of circuit breaker rating).

Default rating is 70% of breaker capacity.

Alarm activates after a user defined time limit (default is
0 seconds)

a

a

Current High Alarm:



A, B, C (circuit breaker 1),
A, B, C (circuit breaker 2)

Indicates current exceeds user defined threshold (ex-
pressed as a percentage of circuit breaker rating).

Default rating is 85% of breaker capacity.

Alarm activates after a user defined time limit (default is
10 seconds)

a

a

Global Alarms:

Current Warning Alarm

Indicates if any current warning alarm is active.

a

a

High Current Alarm

Indicates if any high current alarm is active

a

a

Overvoltage Alarm

Indicates if any over voltage alarm is active

a

Undervoltage Alarm

Indicates if any under voltage alarm is active

a

Overvoltage Alarm:

(L-N Voltage)

Indicates voltage exceeds user defined threshold

a

Undervoltage Alarm:

(L-N Voltage)

Indicates voltage is below user defined threshold

a

Digital Input Alarm:

Digital inputs 1, 2, 3, 4

Indicates closed status of dry contact digital inputs (for
customer use)

a