Series dpb busway installation & operation manual – GE Industrial Solutions GE Zenith Series DPB User Manual

Page 75

Advertising
background image

67

Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

Series DPB Busway Installation & Operation Manual

BCMS Basic = Current Only
BCMS Plus = Current + Voltage

PERSONALIZATION

PARAMETER

DESCRIPTION

RESOLUTION

NOTES

BCMS

BASIC

BCMS

PLUS

Circuit Breaker Size:

Source circuit breaker rating 1 A

Defines source circuit breaker
rating; default is 250 A (1 A incre-
ments); 50-600 A range

a

a

Warning Time Delay:

Time (seconds) before warn-
ing alarm activates

0-60 seconds

Defines duration current must
exceed threshold before activat-
ing a current default is 0 seconds
warning alarm;

a

a

Alarm Time Delay:

Time (seconds) before alarm
activates

0-60 seconds

Defines duration current must
exceed threshold before activating
a high current alarm; default is 10
seconds

a

a

Demand Average Time:

Time (seconds) to determine
average current

1 second

Defines time by which average
current is determined; default is 15
seconds; range is 15-60 seconds

a

a

Current Warning Alarm:

Circuit breaker current first
level alarm threshold

40-100%

Defines threshold based on a
percentage of circuit breaker rating
(default is 70%) to activate current
warning alarm after a time delay
(default is zero seconds).

a

a

Current High Alarm:

Circuit breaker current sec-
ond level alarm threshold

50-100%

Defines threshold based on a
percentage of circuit breaker rating
(default is 85%) to activate high
current alarm after a time delay
(default is 10 seconds).

a

a

Frequency:

Source frequency

0.1 Hz

Defines frequency (60 Hz or 50 Hz)

a

Board Name Personal-
ization

User defined device name

16 Char

Device name; 16 Character maxi-
mum

a

Overvoltage Alarm:

High voltage detected on
source

0.1V

Defines voltage to activate over
voltage alarm

a

Undervoltage Alarm:

Low voltage detected on
source

0.1V

Defines voltage to activate under
voltage alarm

a