Series DPB Busway Installation & Operation Manual

LED Control – This is used to help find devices on the chain� To use led control you must use the check box beside the
iBus device you wish to find� The “Selected On“ will turn the led on the box on solid for the allotted time in the box below
(in minutes)� The “All Off will turn all the lights back to their current state� Blinking for alarm and off for no alarm�

Default – This will Default the board� Defaulting the board will remove all the setup and convert back to a default state�
You will lose all the Modbus setup, device setup and locations� This is not recommended unless you are moving or
reconfiguring the entire busway�

COMMON PROCEDURES

Removing a Tap Off Box:

If you wish to remove a Tap Off Box you must physically disconnect the Communications Cable from the Tap Off Box and
Busrail Connector� Use “Remove” to remove it from the list� It should now be a “No Device” and the Accumulator will not
look for it anymore� If you do not plan to use this location anymore, you may want to use the “Reserve” and reserve this
spot so any new boxes will be added to the end and not the spot where this box was�

Replacing a Tap Off Box:

If you wish to replace a Tap Off Box and put a new one in its place you must disconnect the old Tap Off Box - see section
Tap Off Box Mounting� Use “Remove” to remove it from the list� Install the new Tap Off Box - see section Tap Off Box
Mounting� As long as it is the first “No Device” in the list is where you want it, it will be added back to the same address�
If not, use the “Swap” command to move it to the previous location�

Adding a Tap Off Box:

If you wish to add a Tap Off Box in the first “No Device” spot or at the end, install the new Tap Off Box - see section Tap
Off Box Mounting� Connect the Communications Cable to the Tap Off Box and and an available Busrail Communications
Connector� If you wish to add it to a reserved spot, you will need to remove the reserved by using the “Remove”
command before installation�