Installation & Operation Manual, GE Series DPB Busway
March 25, 2013, Rev 0

GE Confidential

E Clip

Series DPB Busway Installation & Operation Manual

CABLE TERMINATIONS TO THE END FEED BOX

STANDARD END FEED


Run all conduit fittings and supports;
attach cable to the listed lugs on the
termination pad.


Ensure that phasing is correct
(see Figure 17).

Once complete, torque all connections
with a torque wrench to the values
specified on the label located inside the
End Feed Box.

BRANCH CIRCUIT MONITORING (BCMS)

END FEED


Run all conduit fittings and supports;
attach cable to the listed lugs on the
termination pad.


Ensure that phasing is correct (see Figure
18) and that Current Transformers (CT)
are facing in the correct direction (see
Figure 19). The H1 notation on the CT
should be facing the input power source.

Once complete, torque all connections
with a torque wrench to the values
specified on the label on the End Feed Box.

ØA

ØB

N

ØC

GROUND

Figure 17 - Standard End Feed Cable Terminations

ØA

N

ØB

ØC

CT

GROUND

Figure 18 - Branch Circuit Monitoring (BCMS) End Feed Cable Terminations