2.1.7 Installation at high altitudes (PELV)

Installation at high altitude:
380 - 480 V: At altitudes above 3 km, please contact GE regarding PELV.
525 - 600 V: At altitudes above 2 km, please contact GE regarding PELV.

2.1.8 Avoid unintended start

While the frequency converter is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the
keypad.

Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start.

To avoid unintended start, always activate the [OFF] key before changing parameters.

An electronic fault, temporary overload, a fault in the mains supply, or lost motor connection may cause a stopped motor to start.

2.1.9 IT mains

IT Mains
Do not connect frequency converters with option factory installed A1/B1 RFI filters to mains supplies with a voltage between phase and earth
of more than 440 V for 400 V.
For 400 V IT mains and delta earth (grounded leg), mains voltage may exceed 440 V between phase and earth.

par. SP-50 RFI Filter can be used to disconnect the internal RFI capacitiors from the RFI filter to ground.

2.1.10 Software version and approvals: AF-600 FP Fan & Pump Drive

AF-600 FP

Software version: 2.9.x

This manual can be used with all AF-600 FP frequency converters with software version 2.9x.
The software version number can be seen from par. ID-43 Software Version.

2.1.11 Disposal instruction

Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid legislation.

AF-600 FP High Power Operating Instructions