Par. cl-04 feedback 2 conversion, Par. cl-06 feedback 3 source, Par. cl-07 feedback 3 conversion – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 102: Par. cl-20 feedback function, Af-600 fp high power operating instructions

Advertising
background image

[8]

Analog input X30/12

[9]

Analog Input X42/1

[10]

Analog Input X42/3

[11]

Analog Input X42/5

[100]

Bus feedback 1

[101]

Bus feedback 2

[102]

Bus feedback 3

CL-04 Feedback 2 Conversion

Option:

Function:

See par. CL-01 Feedback 1 Conversion for details.

[0] *

Linear

[1]

Square root

[2]

Pressure to temperature

CL-06 Feedback 3 Source

Option:

Function:

See par. CL-00 Feedback 1 Source for details.

[0] *

No function

[1]

Analog input 53

[2]

Analog input 54

[3]

Pulse input 29

[4]

Pulse input 33

[7]

Analog input X30/11

(OPCGPIO)

[8]

Analog input X30/12

(OPCGPIO)

[9]

Analog Input X42/1

(OPCAIO)

[10]

Analog Input X42/3

(OPCAIO)

[11]

Analog Input X42/5

(OPCAIO)

[100]

Bus feedback 1

[101]

Bus feedback 2

[102]

Bus feedback 3

CL-07 Feedback 3 Conversion

Option:

Function:

See par. CL-01 Feedback 1 Conversion for details.

[0] *

Linear

[1]

Square root

[2]

Pressure to temperature

CL-20 Feedback Function

Option:

Function:

This parameter determines how the three possible feedbacks will be used to control the output frequency
of the frequency converter.

[0]

Sum

Sum [0] sets up the PID Controller to use the sum of Feedback 1, Feedback 2 and Feedback 3 as the
feedback.

AF-600 FP High Power Operating Instructions

100

7

Advertising