Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 157

Advertising
background image

Mains Supply 3 x 380 - 480 VAC

P500

P560

P630

P710

P800

P1M0

Typical Shaft output
at 400 V [kW]

500

560

630

710

800

1000

Typical Shaft output
at 460 V [HP]

650

750

900

1000

1200

1350

Unit Size IP21, 54
without/ with options
cabinet

61/63

61/63

61/63

61/63

62/64

62/64

Output current
Continuous
(at 400 V) [A]

880

990

1120

1260

1460

1720

Intermittent (60 sec
overload)
(at 400 V) [A]

968

1089

1232

1386

1606

1892

Continuous
(at 460 V) [A]

780

890

1050

1160

1380

1530

Intermittent (60 sec
overload)
(at 460 V) [A]

858

979

1155

1276

1518

1683

Continuous KVA
(at 400 V) [KVA]

610

686

776

873

1012

1192

Continuous KVA
(at 460 V) [KVA]

621

709

837

924

1100

1219

Max. input current

Continuous
(at 400 V ) [A]

857

964

1090

1227

1422

1675

Continuous (at 460 V)
[A]

759

867

1022

1129

1344

1490

Max. cable size,motor
[mm

2

(AWG

2)

)]

8x150

(8x300 mcm)

12x150

(12x300 mcm)

Max. cable size,mains
[mm

2

(AWG

2)

)]

8x240

(8x500 mcm)

Max. cable size, load-
sharing [mm

2

(AWG

2)

)]

4x120

(4x250 mcm)

Max. cable size, brake
[mm

2

(AWG

2)

)

4x185

(4x350 mcm)

6x185

(6x350 mcm)

Max. external pre-
fuses [A]

1

1600

2000

2500

Estimated power loss
at rated max. load
[W]

4)

Weight,
Unit Size IP21, IP 54
[kg]

1004/ 1299

1004/ 1299

1004/ 1299

1004/ 1299

1246/ 1541

1246/ 1541

Weight Rectifier Mod-
ule [kg]

102

102

102

102

136

136

Weight Inverter Mod-
ule [kg]

102

102

102

136

102

102

Efficiency

4)

0.98

Output frequency

0-600 Hz

Heatsink overtemp.
trip

95 °C

Power card ambient
trip

68 °C

AF-600 FP High Power Operating Instructions