F-10 Electronic Overload

Option:

Function:

The frequency converter determines the motor temperature for motor protection in two different ways:

Via a thermistor sensor connected to one of the analog or digital inputs (par. F-12 Motor Ther-
mistor Input
).

Via calculation of the thermal load, based on the actual load and time. The calculated thermal
load is compared with the rated motor current I

M,N

and the rated motor frequency f

M,N

. The

calculations estimate the need for a lower load at lower speed due to less cooling from the fan
incorporated in the motor.

[0]

No protection

If the motor is continuously overloaded and no warning or trip of frequency converter is wanted.

[1]

Thermistor warning

Activates a warning when the connected thermistor in the motor reacts in the event of motor over-
temperature.

[2]

Thermistor trip

Stops (trips) the frequency converter when the connected thermistor in the motor reacts in the event of
motor over-temperature.

[3]

Elec. OL Warning 1

[4] *

Elec. OL Trip 1

[5]

Elec. OL Warning 2

[6]

Elec. OL Trip 2

[7]

Elec. OL Warning 3

[8]

Elec. OL Trip 3

[9]

Elec. OL Warning 4

[10]

Elec. OL Trip 4

Electronic Overload functions 1-4 will calculate the load when set-up where they were selected is active. For example Elec. OL Warning 3 or Trip 3 starts calculating
when set-up 3 is selected. For the North American market: The Electronic Overload functions provide class 20 motor overload protection in accordance with NEC.

AF-600 FP High Power Operating Instructions