Par. ap-62 broken belt delay, Par. ap-75 short cycle protection, Par. ap-76 interval between starts – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 98: Par. ap-77 minimum run time, Par. b-10 brake function, Par. b-17 over-voltage control, Par. b-00 dc hold current, Af-600 fp high power operating instructions

Advertising
background image

AP-62 Broken Belt Delay

Range:

Function:

10 s*

[0 - 600 s]

Sets the time for which the Broken Belt conditions must be active before carrying out the action selected
in par. AP-60 Broken Belt Function.

AP-75 Short Cycle Protection

Option:

Function:

[0] *

Disabled

Timer set in par. AP-76 Interval between Starts is disabled.

[1]

Enabled

Timer set in par. AP-76 Interval between Starts is enabled.

AP-76 Interval between Starts

Range:

Function:

par. DN-77
s*

[0 to 3600 s]

Sets the time desired as minimum time between two starts. Any normal start command (Start/Jog/Freeze)
will be disregarded until the timer has expired.

AP-77 Minimum Run Time

Range:

Function:

0 s*

[0 - par. AP-76 ]

Sets the time desired as minimum run time after a normal start command (Start/Jog/Freeze). Any normal
stop command will be disregarded until the set time has expired. The timer will start counting following
a normal start command (Start/Jog/Freeze).

The timer will be overridden by a Coast (Inverse) or an External Interlock command.

NB!
Does not work in cascade mode.

B-00 DC Hold Current

Range:

Function:

50 %*

[0 - 160. %]

Enter a value for holding current as a percentage of the rated motor current I

M,N

set in par. P-03 Motor

Current. 100% DC holding current corresponds to I

M,N

.

This parameter holds the motor (holding torque) or pre-heats the motor.
This parameter is active if [1] DC hold/Preheat is selected in par. H-80 Function at Stop.

NB!
The maximum value depends on the rated motor current.
NB!
Avoid 100 % current for too long. It may damage the motor.

B-10 Brake Function

Option:

Function:

[0] *

Off

No brake resistor installed.

Brake resistor incorporated in the system, for dissipation of surplus brake energy as heat. Connecting a
brake resistor allows a higher DC link voltage during braking (generating operation). The Resistor brake
function is only active in frequency converters with an integral dynamic brake.

B-17 Over-voltage Control

Option:

Function:

Over-voltage control (OVC) reduces the risk of the frequency converter tripping due to an over voltage on
the DC link caused by generative power from the load.

[0]

Disabled

No OVC required.

[2] *

Enabled

Activates OVC.

AF-600 FP High Power Operating Instructions

97

7

Advertising