Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 160

Advertising
background image

Mains Supply 3 x 525- 600 VAC

P400

P450

P500

Typical Shaft output at 550 V [kW]

400

450

500

Typical Shaft output at 575 V [HP]

500

600

650

Unit Size IP21

51

51

51

Unit Size IP54

51

51

51

Unit Size IP00

52

52

52

Output current
Continuous
(at 550 V) [A]

523

596

630

Intermittent (60 sec overload)
(at 550 V) [A]

575

656

693

Continuous
(at 575 V) [A]

500

570

630

Intermittent (60 sec overload)
(at 575 V) [A]

550

627

693

Continuous KVA
(at 550 V) [KVA]

498

568

600

Continuous KVA
(at 575 V) [KVA]

498

568

627

Max. input current

Continuous
(at 550 V ) [A]

504

574

607

Continuous
(at 575 V) [A]

482

549

607

Max. cable size, mains, motor and
load share [mm

2

(AWG)]

4x240 (4x500 mcm)

4x240 (4x500 mcm)

4x240 (4x500 mcm)

Max. cable size, brake [mm

2

(AWG)]

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

2 x 185

(2 x 350 mcm)

Max. external pre-fuses [A]

1

700

900

900

Estimated power loss
at rated max. load [W]

4)

7249

8727

9673

Weight,
Unit Size IP21, IP 54 [kg]

263

272

313

Weight,
Unit Size IP00 [kg]

221

236

277

Efficiency

4)

0.98

Output

frequency

0 - 500 Hz

Heatsink overtemp. trip

85 °C

Power card ambient trip

68 °C

AF-600 FP High Power Operating Instructions

158

8

Advertising