Par. f-17 motor speed high limit [rpm, Par. f-18 motor speed low limit [rpm, Par. f-18 motor speed low limit [rpm] o – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 88

Advertising
background image

F-17 Motor Speed High Limit [RPM]

Range:

Function:

1500. RPM* [par. H-11 - 60000. RPM]

Enter the maximum limit for motor speed. The Motor Speed High Limit can be set to correspond to the
manufacturer’s maximum rated motor. The Motor Speed High Limit must exceed the setting in par.
F-18 Motor Speed Low Limit [RPM]
. Only par. F-18 Motor Speed Low Limit [RPM] or par. F-16 Motor Speed
Low Limit [Hz]
will be displayed depending on other parameters in the Main Menu and depending on
default settings dependant on global location.

NB!
The output frequency value of the frequency converternot exceed a value higher than 1/10 of the switching frequency.

NB!
Any changes in par. F-17 Motor Speed High Limit [RPM] will reset the value in par. H-73 Warning Speed High to the same value as set in par. F-17 Motor Speed
High Limit [RPM]
.

F-18 Motor Speed Low Limit [RPM]

Range:

Function:

0 RPM*

[0 - par. H-13 RPM]

Enter the minimum limit for motor speed. The Motor Speed Low Limit can be set to correspond to the
manufacturer’s recommended minimum motor speed. The Motor Speed Low Limit must not exceed the
setting in par. F-17 Motor Speed High Limit [RPM].

C-20 Jog Speed [Hz]

Range:

Function:

10.0 Hz*

[0.0 - par. H-14 Hz]

The jog speed is a fixed output speed at which the frequency converter is running when the jog function
is activated.
See also par. C-22 Jog Accel/Decel Time.

AF-600 FP High Power Operating Instructions

87

7

Advertising