Af-600 fp high power operating instructions, 14 motor insulation – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 26

Advertising
background image

525-600 V, unit sizes 4X, 5X and 6X

AF-600 FP

Bussmann

E125085

JFHR2

Amps

SIBA

E180276

JFHR2

Ferraz-Shawmut

E76491

JFHR2

Internal

Option

Bussmann

150 HP

170M3017

315

2061032.315

6.6URD30D08A0315

170M3018

200 HP

170M3018

350

2061032.35

6.6URD30D08A0350

170M3018

250 HP

170M4011

350

2061032.35

6.6URD30D08A0350

170M5011

300 HP

170M4012

400

2061032.4

6.6URD30D08A0400

170M5011

350 HP

170M4014

500

2061032.5

6.6URD30D08A0500

170M5011

400 HP

170M5011

550

2062032.55

6.6URD32D08A550

170M5011

Table 3.7: Unit Size 41, 42, 43, and 44, 525-600 V

AF-600 FP

Bussmann PN*

Rating

Ferraz

Siba

450 HP

170M4017

700 A, 700 V

6.9URD31D08A0700

20 610 32.700

500 HP

170M4017

700 A, 700 V

6.9URD31D08A0700

20 610 32.700

600 HP

170M6013

900 A, 700 V

6.9URD33D08A0900

20 630 32.900

650 HP

170M6013

900 A, 700 V

6.9URD33D08A0900

20 630 32.900

Table 3.8: Unit Sizes 51 and 52, 525-600 V

AF-600 FP

Bussmann PN*

Rating

Siba

Internal Bussmann Option

750 HP

170M7081

1600 A, 700 V

20 695 32.1600

170M7082

950 HP

170M7081

1600 A, 700 V

20 695 32.1600

170M7082

1050 HP

170M7081

1600 A, 700 V

20 695 32.1600

170M7082

1150 HP

170M7081

1600 A, 700 V

20 695 32.1600

170M7082

1350 HP

170M7082

2000 A, 700 V

20 695 32.2000

170M7082

Table 3.9: Unit Sizes 61, 62, 63, and 64, 525-600 V

AF-600 FP

Bussmann PN*

Rating

Siba

750 HP

170M8611

1100 A, 1000 V

20 781 32. 1000

950 HP

170M8611

1100 A, 1000 V

20 781 32. 1000

1050 HP

170M8611

1100 A, 1000 V

20 781 32. 1000

1150 HP

170M8611

1100 A, 1000 V

20 781 32. 1000

1350 HP

170M8611

1100 A, 1000 V

20 781 32. 1000

Table 3.10: Unit Sizes 61, 62, 63, and 64, 525-600 V

*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use.

3.1.14 Motor Insulation

For motor cable lengths

≤ the maximum cable length listed in the General Specifications tables the following motor insulation ratings are recommended because

the peak voltage can be up to twice the DC link voltage, 2.8 times the mains voltage, due to transmission line effects in the motor cable. If a motor has lower
insulation rating it recommended to use a du/dt or sine wave filter.

Nominal Mains Voltage

Motor Insulation

U

N

≤ 420 V

Standard U

LL

= 1300 V

420 V < U

N

≤ 500 V

Reinforced U

LL

= 1600 V

500 V < U

N

≤ 600 V

Reinforced U

LL

= 1800 V

AF-600 FP High Power Operating Instructions

25