Af-600 fp high power operating instructions, 2 quick menu mode – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 84

Advertising
background image

7.1.2 Quick Menu Mode

Parameter Data
The keypad provides access to all parameters listed under the Quick Menus. To set parameters using the [Quick Menu] button - enter or change parameter data
or settings in accordance with the following procedure:

1.

Press Quick Menu button then press Quick Start

2.

Use the [

] and [

] buttons to find the parameter you want to change

3.

Press [OK]

4.

Use [

] and [

] buttons to select the correct parameter setting

5.

Press [OK]

6.

To move to a different digit within a parameter setting, use the [

] and [

] buttons

7.

Highlighted area indicates digit selected for change

8.

Press [Cancel] button to disregard change, or press [OK] to accept change and enter the new setting

Example of Changing Parameter Data
Assume parameter F-07 Accel Time 1 is set to 6 seconds and you want to change it to 10 seconds. Use the following procedure:

1.

Press Quick Menu key

2.

Choose Quick Start

3.

Press [OK]

4.

With the [

] button find par. F-07 Accel Time 1

5.

Press [OK]

6.

Use the arrow keys to change the 6.00 to 10.00.

7.

Press [OK]

The drive will now accelerate to rated speed in 10 seconds instead of 6 seconds.

It is recommended to do the set-up in the order that the parameters are listed!

If [No Operation] is selected in par. E-03 Terminal 27 Digital Input, no connection to +24 V on terminal 27 is necessary to enable start.
If [Coast Inverse] (factory default value) is selected in par. E-03 Terminal 27 Digital Input, a connection to +24V is necessary to enable start.

Select [Parameter Data Check] to get information about:

the last 10 changes. Use the up/down navigation keys to scroll between the last 10 changed parameters.

the changes made since default setting.

Select [Trendings] to get information about the display line read-outs. The information is shown as graphs.
Only display parameters selected in par. K-20 Display Line 1.1 Small and par. K-24 Display Line 3 Large can be viewed. It is possible to store up to 120 samples in
the memory for later reference.

Efficient Parameter Set-up for AF-600 FP Applications
The parameters can easily be set up for the vast majority of the AF-600 FP applications only by using the [Quick Setup] option.
After pressing [Quick Menu], the different choices in the Quick Menu are listed.

Example of using the Quick Setup option

NB!
A complete description of the function is found in the parameter sections of this manual.

AF-600 FP High Power Operating Instructions

83

7

Advertising