Af-600 fp high power operating instructions – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 94

Advertising
background image

AN-50 Terminal 42 Output

Option:

Function:

Select the function of Terminal 42 as an analog current output.

[0] *

No operation

[100]

Output frequency

0 - 100 Hz

[101]

Reference

Minimum reference - Maximum reference

[102]

Feedback

-200% to +200% of par. 20-14

[103]

Motor Current

: 0 - Inverter Max. Current (par. DR-37 Drive Max. Current)

[104]

Torque rel to limit

: 0 - Torque limit (par. F-40 Torque Limiter (Driving))

[105]

Torq relate to rated

: 0 - Motor rated torque

[106]

Power

0 - Motor rated power

[107]

Speed

0 - Speed High Limit (par. F-17 Motor Speed High Limit [RPM] and par. F-15 Motor Speed High Limit [Hz])

[113]

Ext. Closed Loop 1

0 - 100%

[114]

Ext. Closed Loop 2

0 - 100%

[115]

Ext. Closed Loop 3

0 - 100%

[130]

Output freq. 4-20mA

0 - 100 Hz

[131]

Reference 4-20mA

Minimum Reference - Maximum Reference

[132]

Feedback 4-20mA

-200% to +200% of par. 2-14

[133]

Motor cur. 4-20mA

0 - Inverter Max. Current (par. DR-37 Drive Max. Current)

[134]

Torq.% lim 4-20 mA

:0 - Torque limit (par. F-40 Torque Limiter (Driving))

[135]

Torq.% nom 4-20mA

0 - Motor rated torque

[136]

Power 4-20mA

0 - Motor rated power

[137]

Speed 4-20mA

0 - Speed High Limit (par. 4-13 and par. 4-14)

[139]

Bus ctrl.

0 - 100%

[140]

Bus ctrl. 4-20 mA

0 - 100%

[141]

Bus ctrl t.o.

0 - 100%

[142]

Bus ctrl t.o. 4-20mA

0 - 100%

[143]

Ext. CL 1 4-20mA

0 - 100%

[144]

Ext. CL 2 4-20mA

0 - 100%

[145]

Ext. CL 3 4-20mA

0 - 100%

NB!
Values for setting the Minimum Reference is found in open loop par. F-52 Minimum Reference and for closed loop par. CL-13 Minimum Reference/Feedb. - values
for maximum reference for open loop is found in par. F-53 Maximum Reference and for closed loop par. CL-14 Maximum Reference/Feedb..

AN-51 Terminal 42 Output Min Scale

Range:

Function:

0.00 %*

[0.00 - 200.00 %]

Scale for the minimum output (0 or 4 mA) of the analogue signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. AN-50 Terminal 42
Output
.

AF-600 FP High Power Operating Instructions

93

7