NB!
A doorfan(s) is required on the Rittal cabinet to remove the loses not contained in the backchannel of the drive. The minimum doorfan(s) airflow required at the
drive maximum ambient for the 43 and 44 is 391 m^3/h (230 cfm). The minimum doorfan(s) airflow required at the drive maximum ambient for the 52 is 782
m^3/h (460 cfm). If the ambient is below maximum or if additional components, heat loses, are added within the Unit a calculation must be made to ensure the
proper airflow is provided to cool the inside of the Rittal Unit.

Ordering Information

Rittal TS-8 Unit

Unit Size 43 Kit Part No.

Unit Size 44Kit Part No.

Unit Size 52 Part No.

1800 mm

Consult GE

Consult GE

Not possible

2000 mm

Consult GE

Consult GE

Consult GE

2200 mm

Consult GE

Kit Contents

Ductwork components

Mounting hardware

Gasket material

Delivered with Unit Sizes 43 and 44 kits:

Mounting templates and top/bottom cut out for Rittal Unit.

Delivered with Unit Size 52 kits:

Mounting templates and top/bottom cut out for Rittal Unit.

All fasteners are either:

10 mm, M5 Nuts torque to 2.3 Nm (20 in-lbs)

T25 Torx screws torque to 2.3 Nm (20 in-lbs)

NB!
Please consult GE for more details on duct kits for AF-600 FP drives