NB!
The decel ramp time is automatically adjusted to avoid tripping of the frequency converter.

C-05 Multi-step Frequency 1 - 8

Array [8]

Range:

Function:

0.00 %*

[-100.00 - 100.00 %]

Enter up to eight different preset references (0-7) in this parameter, using array programming. The preset
reference is stated as a percentage of the value Ref

MAX

(par. F-53 Maximum Reference, for closed loop

see par. CL-14 Maximum Reference/Feedb.). When using preset references, select Preset ref. bit 0 / 1 / 2
[16], [17] or [18] for the corresponding digital inputs in parameter group E-## Digital Inputs.

C-30 Frequency Command 2

Option:

Function:

Select the reference input to be used for the second reference signal. par. F-01 Frequency Setting 1, par.
C-30 Frequency Command 2 an
d par. C-34 Frequency Command 3 define up to three different reference
signals. The sum of these reference signals defines the actual reference.

This parameter cannot be adjusted while the motor is running.

[0]

No function

[1]

Analog input 53

[2]

Analog input 54

[7]

Pulse input 29

[8]

Pulse input 33

[20] *

Digital Potentiometer

[21]

Analog input X30/11

(OPCGPIO)

[22]

Analog input X30/12

(OPCGPIO)

[23]

Analog Input X42/1

(OPCAIO)

[24]

Analog Input X42/3

(OPCAIO)

[25]

Analog Input X42/5

(OPCAIO)

[30]

Ext. Closed Loop 1

[31]

Ext. Closed Loop 2

[32]

Ext. Closed Loop 3

C-40 Semi-Auto Jump Freq Set-up

Option:

Function:

[0] *

Off

No function

[1]

Enabled

Starts the Semi-Automatic Bypass set-up and continue with the procedure described above.

AF-600 FP High Power Operating Instructions

98