ALARM 245, Heatsink sensor:
Unit size 6 equivalent to fault 39 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 246, Pwr. card supply:
Unit size 6 equivalent to fault 46 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 247, Pwr. card temp:
Unit size 6 equivalent to fault 69 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 248, Illegal PS config:
Unit size 6 equivalent to fault 79 in Unit sizes 4X and 5X. Report value indicates
source of the alarm (from left):
0-3 Inverter
4-7 Rectifier

ALARM 250, New Spare Part:
The power or Switch Mode Power Supply has been exchanged. The frequency
converter type code must be restored in the EEPROM. Remember to select
‘Save to EEPROM’ to complete.

ALARM 251, New Type Code:
The Frequency Converter has got a new GE Model Number.

AF-600 FP High Power Operating Instructions