Surroundings:

Enclosure, frame size 4X and 5X

IP 00, IP 21, IP 54

Enclosure, frame size 6X

IP 21, IP 54

Vibration test

0.7 g

Relative humidity

5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation

Aggressive environment (IEC 721-3-3), uncoated

class 3C2

Aggressive environment (IEC 721-3-3), coated

class 3C3

Test method according to IEC 60068-2-43 H2S (10 days)

- with derating

max. 55

° C

1)

- with full output power, typical EFF2 motors

max. 50

° C

1)

- at full continuous drive output current

max. 45

° C

1)

1)

For more information on derating see the AF-600 FP, section on Special Conditions.

Minimum ambient temperature during full-scale operation

0 °C

Minimum ambient temperature at reduced performance

- 10 °C

Temperature during storage/transport

-25 - +65/70 °C

Maximum altitude above sea level without derating

1000 m

Maximum altitude above sea level with derating

3000 m

Derating for high altitude, see section on special conditions

EMC standards, Emission

EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3

EMC standards, Immunity

EN 61800-3, EN 61000-6-1/2,

EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6

See section on special conditions!

Control card performance:

Scan interval

: 5 ms

Control card, USB serial communication:

USB standard

1.1 (Full speed)

USB plug

USB type B “device” plug

Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection earth. Use only isolated laptop/PC as connection to the USB connector on VLT
AQUA Drive or an isolated USB cable/converter.

Protection and Features:

Electronic thermal motor protection against overload.

Temperature monitoring of the heatsink ensures that the frequency converter trips if the temperature reaches 95 °C ± 5°C. An overload temperature
cannot be reset until the temperature of the heatsink is below 70 °C ± 5°C (Guideline - these temperatures may vary for different power sizes, enclosures
etc.). AF-600 FP Drive has an auto derating function to avoid it's heatsink reaching 95 deg C.

The frequency converter is protected against short-circuits on motor terminals U, V, W.

If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).

Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.

The frequency converter is protected against earth faults on motor terminals U, V, W.

AF-600 FP High Power Operating Instructions

152