Closed Loop Settings

Single Zone Int. Set Point

Single Zone Ext. Set Point

Multi Zone / Adv

par. H-40 Configuration Mode

par. H-40 Configuration Mode

par. H-40 Configuration Mode

par. CL-12 Reference/Feedback Unit

par. CL-12 Reference/Feedback Unit

par. F-01 Frequency Setting 1

par. CL-13 Minimum Reference/Feedb.

par. CL-13 Minimum Reference/Feedb.

par. C-30 Frequency Command 2

par. CL-14 Maximum Reference/Feedb.

par. CL-14 Maximum Reference/Feedb.

par. CL-00 Feedback 1 Source

par. AN-22 Terminal 54 Low Current

par. AN-10 Terminal 53 Low Voltage

par. CL-01 Feedback 1 Conversion

par. AN-24 Terminal 54 Low Ref./Feedb. Value

par. AN-11 Terminal 53 High Voltage

par. CL-02 Feedback 1 Source Unit

par. AN-25 Terminal 54 High Ref./Feedb. Value

par. AN-12 Terminal 53 Low Current

par. CL-03 Feedback 2 Source

par. AN-26 Terminal 54 Filter Time Constant

par. AN-13 Terminal 53 High Current

par. CL-04 Feedback 2 Conversion

par. AN-27 Terminal 54 Live Zero

par. AN-14 Terminal 53 Low Ref./Feedb. Value

par. CL-05 Feedback 2 Source Unit

par. AN-00 Live Zero Timeout Time

par. AN-15 Terminal 53 High Ref./Feedb. Value

par. CL-06 Feedback 3 Source

par. AN-01 Live Zero Timeout Function

par. AN-22 Terminal 54 Low Current

par. CL-07 Feedback 3 Conversion

par. CL-21 Setpoint 1

par. AN-24 Terminal 54 Low Ref./Feedb. Value

par. CL-08 Feedback 3 Source Unit

par. CL-81 PID Normal/ Inverse Control

par. AN-25 Terminal 54 High Ref./Feedb. Value

par. CL-12 Reference/Feedback Unit

par. CL-82 PID Start Speed [RPM]

par. AN-26 Terminal 54 Filter Time Constant

par. CL-13 Minimum Reference/Feedb.

par. CL-83 PID Start Speed [Hz]

par. AN-27 Terminal 54 Live Zero

par. CL-14 Maximum Reference/Feedb.

par. CL-93 PID Proportional Gain

par. AN-00 Live Zero Timeout Time

par. AN-10 Terminal 53 Low Voltage

par. CL-94 PID Integral Time

par. AN-01 Live Zero Timeout Function

par. AN-11 Terminal 53 High Voltage

par. CL-81 PID Normal/ Inverse Control

par. AN-12 Terminal 53 Low Current

par. CL-82 PID Start Speed [RPM]

par. AN-13 Terminal 53 High Current

par. CL-83 PID Start Speed [Hz]

par. AN-14 Terminal 53 Low Ref./Feedb. Value

par. CL-93 PID Proportional Gain

par. AN-15 Terminal 53 High Ref./Feedb. Value

par. CL-94 PID Integral Time

par. AN-16 Terminal 53 Filter Time Constant
par. AN-17 Terminal 53 Live Zero
par. AN-20 Terminal 54 Low Voltage
par. AN-21 Terminal 54 High Voltage
par. AN-22 Terminal 54 Low Current
par. AN-23 Terminal 54 High Current
par. AN-24 Terminal 54 Low Ref./Feedb. Value
par. AN-25 Terminal 54 High Ref./Feedb. Value
par. AN-26 Terminal 54 Filter Time Constant
par. AN-27 Terminal 54 Live Zero
par. AN-00 Live Zero Timeout Time
par. AN-01 Live Zero Timeout Function
par. H-76 Warning Feedback Low
par. H-77 Warning Feedback High
par. CL-20 Feedback Function
par. CL-21 Setpoint 1
par. CL-22 Setpoint 2
par. CL-81 PID Normal/ Inverse Control
par. CL-82 PID Start Speed [RPM]
par. CL-83 PID Start Speed [Hz]
par. CL-93 PID Proportional Gain
par. CL-94 PID Integral Time
par. CL-70 Closed Loop Type
par. CL-71 PID Performance
par. CL-72 PID Output Change
par. CL-73 Minimum Feedback Level
par. CL-74 Maximum Feedback Level
par. CL-79 PID Autotuning

See also AF-600 FP Programming Guide for a detailed description of the Quick Menu parameter groups.

AN-00 Live Zero Timeout Time

Range:

Function:

10 s*

[1 - 99 s]

Enter the Live Zero Time-out time period. Live Zero Time-out Time is active for analog inputs, i.e. terminal
53 or terminal 54, allocated to current and used as reference or feedback sources. If the reference signal
value associated with the selected current input falls below 50% of the value set in par. AN-10 Terminal
53 Low Voltage
, par. AN-12
Terminal 53 Low Current, par. AN-20 Terminal 54 Low Voltage or par.
AN-22 Terminal 54 Low Current for a time period longer than the time set in par. AN-00 Live Zero Timeout
Time
, the function selected in par. AN-01 Live Zero Timeout Function will be activated.

AN-01 Live Zero Timeout Function

Option:

Function:

Select the time-out function. The function set in par. AN-01 Live Zero Timeout Function will be activated
if the input signal on terminal 53 or 54 is below 50% of the value in par. AN-10 Terminal 53 Low Voltage,
par. AN-12 Terminal 53 Low Current, par. AN-20 Terminal 54 Low Voltage or par. AN-22 Terminal 54 Low
Current
for a time period defined in par. AN-00 Live Zero Timeout Time. If several time-outs occur simul-
taneously, the frequency converter prioritises the time-out functions as follows:

AF-600 FP High Power Operating Instructions

90