Par. an-10 terminal 53 low voltage, Par. an-11 terminal 53 high voltage, Par. an-14 terminal 53 low ref./feedb. value – GE Industrial Solutions AF-600 FP Fan and Pump Drive (460V_575V 150HP and above) User Manual

Page 92: Par. an-15 terminal 53 high ref./feedb. value, Par. an-10 terminal 53 low voltage , par. an-12, Af-600 fp high power operating instructions

Advertising
background image

1.

par. AN-01 Live Zero Timeout Function

2.

par. O-04 Control Word Timeout Function

The output frequency of the frequency converter can be:

[1] frozen at the present value

[2] overruled to stop

[3] overruled to jog speed

[4] overruled to max. speed

[5] overruled to stop with subsequent trip

[0] *

Off

[1]

Freeze output

[2]

Stop

[3]

Jogging

[4]

Max. speed

[5]

Stop and trip

AN-10 Terminal 53 Low Voltage

Range:

Function:

0.07 V*

[0.00 - par. AN-11 V]

Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par. AN-14 Terminal 53 Low Ref./Feedb. Value.

AN-11 Terminal 53 High Voltage

Range:

Function:

10.00 V*

[par. AN-10 - 10.00 V]

Enter the high voltage value. This analog input scaling value should correspond to the high reference/
feedback value set in par. AN-15 Terminal 53 High Ref./Feedb. Value.

AN-14 Terminal 53 Low Ref./Feedb. Value

Range:

Function:

0.000 N/A* [-999999.999 - 999999.999 N/A]

Enter the analog input scaling value that corresponds to the low voltage/low current set in par.
AN-10 Terminal 53 Low Voltage an
d par. AN-12 Terminal 53 Low Current.

AN-15 Terminal 53 High Ref./Feedb. Value

Range:

Function:

50.000 N/A* [-999999.999 - 999999.999 N/A]

Enter the analog input scaling value that corresponds to the high voltage/high current value set in par.
AN-11 Terminal 53 High Voltage an
d par. AN-13 Terminal 53 High Current.

AF-600 FP High Power Operating Instructions

91