AN-16 Terminal 53 Filter Time Constant

Range:

Function:

0.001 s*

[0.001 - 10.000 s]

Enter the time constant. This is a first-order digital low pass filter time constant for suppressing electrical
noise in terminal 53. A high time constant value improves dampening but also increases the time delay
through the filter.
This parameter cannot be adjusted while the motor is running.

AN-17 Terminal 53 Live Zero

Option:

Function:

This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog outputs
are used as part of a decentral I/O system (e.g. when not part of any frequency converter related control
functions, but feeding a Building Management system with data)

[0]

Disabled

[1] *

Enabled

AN-20 Terminal 54 Low Voltage

Range:

Function:

0.07 V*

[0.00 - par. AN-21 V]

Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value, set in par. AN-24 Terminal 54 Low Ref./Feedb. Value.

AN-21 Terminal 54 High Voltage

Range:

Function:

10.00 V*

[par. AN-20 - 10.00 V]

Enter the high voltage value. This analog input scaling value should correspond to the high reference/
feedback value set in par. AN-25 Terminal 54 High Ref./Feedb. Value.

AN-24 Terminal 54 Low Ref./Feedb. Value

Range:

Function:

0.000 N/A* [-999999.999 - 999999.999 N/A]

Enter the analog input scaling value that corresponds to the low voltage/low current value set in par.
AN-20 Terminal 54 Low Voltage
and par. AN-22 Terminal 54 Low Current.

AN-25 Terminal 54 High Ref./Feedb. Value

Range:

Function:

100.000 N/
A*

[-999999.999 - 999999.999 N/A]

Enter the analog input scaling value that corresponds to the high voltage/high current value set in par.
AN-21 Terminal 54 High Voltage an
d par. AN-23 Terminal 54 High Current.

AN-26 Terminal 54 Filter Time Constant

Range:

Function:

0.001 s*

[0.001 - 10.000 s]

Enter the time constant. This is a first-order digital low pass filter time constant for suppressing electrical
noise in terminal 54. A high time constant value improves dampening but also increases the time delay
through the filter.
This parameter cannot be adjusted while the motor is running.

AN-27 Terminal 54 Live Zero

Option:

Function:

This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog outputs
are used as part of a decentral I/O system (e.g. when not part of any frequency converter related control
functions, but feeding a Building Management System with data)

[0]

Disabled

[1] *

Enabled